Advanced features of this UPS system include intelligent battery management, remote monitoring and control, as well as automatic battery testing, providing a comprehensive power management solution. The EA990RT G5 10kVA–60kVA UPS system, with its high-frequency design, offers users reliable and efficient power protection, making it an ideal choice for applications with stringent power stability requirements.
Product Description
The EA990RT G5 is a high-frequency, three-phase input and three-phase output UPS (uninterruptible power supply) system designed to meet power requirements ranging from 10 kVA to 60 kVA. This UPS system utilizes advanced technology to deliver excellent power protection and reliability, making it suitable for various critical applications.
Features
Rear Panel
Specification
MODEL |
EA9910RT |
EA9915RT |
EA9920RT |
EA9930RT |
EA9940RT |
EA9960RT |
|
Capacity |
10kVA/10kW |
15kVA/15kW |
20kVA/20kW |
30kVA/30kW |
40kVA/40kW |
60kVA/60kW |
|
INPUT |
|||||||
Rated voltage |
380/400/415Vac (3Φ + N + PE) |
||||||
Voltage range |
304~478Vac, full load 228 V~304Vac, load decrease linearly according to the min phase voltage |
||||||
Rated frequency |
50/60Hz(auto-sensing) |
||||||
Frequency range |
40~70Hz |
||||||
Power factor |
> 0.99 |
||||||
Bypass voltage range |
Selectable, default -20%~+15% Up limited: +10%, +15%, +20%, +25%; Down limited: -10%, -15%, -20%, -30%, -40% |
||||||
Bypass frequency range |
Selectable, ±1Hz, ±3Hz, ±5Hz |
||||||
Total harmonic distortion (THDi) |
<3% (full linear load) |
||||||
Bypass overload |
125%: Long term operation; 125%~130%: 10min; 130%~150%: 1min; 150%~400%: 1s; >400%, less than 200ms |
||||||
OUTPUT |
|||||||
Rated voltage |
380/400/415Vac (3Φ + N + PE) |
||||||
Voltage regulation |
±1% (full linear load) |
||||||
Frequency |
Synchronized with utility in mains mode, 50/60Hz ±0.1% in battery mode |
||||||
Waveform |
Sinusoidal |
||||||
Power factor |
1 |
||||||
Total harmonic distortion (THDv) |
<1% (full linear load); <3% (full non-linear load according to IEC/EN62040-3) |
||||||
Crest factor |
3:1 |
||||||
Overload |
<110%, 60min; 110%~125%,10min; 125%~150%,1min; >150%, 200ms |
||||||
BATTERIES |
|||||||
DC voltage |
±240VDC(selectable, 32 - 40pcs) |
||||||
Charging current |
10A max |
15A |
20A |
||||
Charger voltage precision |
1% |
||||||
Recharge time |
Long time model: depend on the capacity of battery |
||||||
SYSTEM |
|||||||
Efficiency |
95% Max |
96% Max |
|||||
Transfer time |
0ms |
||||||
Max. number of parallel connections |
4 |
||||||
Protections |
Short-circuit, overload, overtemperature, battery low voltage, overvoltage, undervoltage and fan failure |
||||||
Communications |
Sandard: RS232, USB, RS485, EPO, Dry contacts, Parallel port Optional: SNMP card, WI-FI card, GPRS card, SMS alarms |
||||||
Display |
LED + 5 inches LCD touch screen |
||||||
OTHERS |
|||||||
Operating temperature |
0℃~40℃ |
||||||
Storage temperature |
-40℃~70 ℃ |
||||||
Relative humidity |
0 ~ 95% (non-condensing) |
||||||
Altitude |
<1000m, load derated 1% per 100m from 1000 ~ 2000m |
||||||
IP rating |
IP 20 |
||||||
Noise level at 1m |
<60dB |
<65dB |
|||||
Dimensions (W×D×H) (mm) |
440*660*130 |
440*750*130 |
440*730*130 |
440*800*130 |
|||
Packaged dimensions (W×D×H) (mm) |
532*800*204 |
532*890*204 |
535*865*226 |
535*930*226 |
|||
Net weight (kg) |
22 |
24 |
29 |
33 |
39 |
||
Gross weight (kg) |
24 |
26 |
31 |
36 |
42 |