The EA660 Series modular UPS is ideal for reliable, cost-saving, intelligent, and easy solutions. It ensures that a scalable, secure, high-quality power supply is available for any critical high-density computer and IT environment applications, such as data centers and other critical loads.
Product Description
The EA660 Series (15 kVA~120 kVA) UPS is a high-end modular UPS with the latest dual-core DSP control technology. It adopts a highly intelligent modular design that mainly contains power modules, bypass modules, and control modules. All modules support plug & play to simplify UPS servicing and maintenance. The available UPS power and redundancy level can expand vertically from 15 kVA/15 kW to 120 kVA/120 kW in one single power cabinet with flexible configuration for meeting different needs. Based on superior electrical performance and perfect hardware and software protection functions, the EA660 Series UPS can adapt to different grid environments and provide maximum protection and high-quality power for critical loads in data centers or other important applications.
Features
Specification
MODEL |
EA6660_LV |
EA66120_LV |
|
Rated capacity |
60kVA/60kW |
120kVA/120kW |
|
Number of power module |
4 |
8 |
|
Rated capacity of power module |
15kVA/15kW |
||
INPUT |
|||
Input wiring |
Three-phase five-wire (3Φ+N+PE) |
||
Rated voltage |
190/208/220Vac |
||
Voltage range |
166~277Vac (no downgrading), 114~166Vac (linear downgrading between 40%~100% load) |
||
Frequency range |
40~70Hz |
||
Input power factor |
≥ 0.99 |
||
THDi |
≤ 3% |
||
Bypass input voltage range |
-40%~+25% (settable) |
||
Battery voltage |
±120VDC(±96V,±108V,±120V,±132V,±144V settable) |
||
Number of battery |
20pcs 12V batteries (16, 18, 20, 22, 24pcs settable) |
||
OUTPUT |
|||
Output wiring |
Three-phase five-wire (3Φ+N+PE) |
||
Rated voltage |
190/208/220Vac |
||
Output voltage regulation accuracy |
±1% |
||
Output frequency accuracy |
Synchronized with utility in mains power mode; 50Hz/ 60Hz±0.1% in battery mode |
||
Output power factor |
1 |
||
Output waveform distortion (THDv) |
≤ 2% (linear load); ≤ 5% (non-linear load) |
||
Crest factor |
3:1 |
||
Overload capacity |
105% < load ≤ 110% for 60min, 110% < load ≤ 125% for 10min, 125% < load ≤ 150% for 1min, load > 150% for 0.2s |
||
SYSTEM |
|||
Max. efficiency |
94% in on-line mode, 99% in ECO mode |
||
Transfer time |
0ms |
||
Max. number of parallel connections |
2 |
||
Protections |
Short-circuit, overload, over-temperature, battery low voltage, undervoltage, overvoltage, fan failure protection |
||
Communications |
Standard configurations: RS485, CAN, NET, SNMP, dry contacts port, and EPO Optional configurations: Wi-Fi card, parallel port, LBS port, GPRS card, Battery temperature sensor, EMD and SMS alarms |
||
Display |
7 inches LCD touch screen |
||
ENVIRONMENTAL |
|||
Operating temperature |
0℃ ~40℃ |
||
Storage temperature |
-25℃~+55℃ (without battery) |
||
Relative humidity |
0%~95% (non-condensing) |
||
Altitude |
≤ 1000m, above 1000 m, derating 1% for each additional 100m |
||
Protection level |
IP 20 |
||
Noise |
≤ 65dB (at 1m) |
||
OTHERS |
|||
Cabinet dimensions (WxDxH) (mm) |
600x850x1200 |
600x850x2000 |
|
Cabinet weight (kg) |
180 |
280 |
|
Module dimensions (WxDxH) (mm) |
442x620x86 |
||
Power module weight (kg) |
20.26 |
||
Color |
Black |