The EA660 modular UPS is ideal for reliable, cost-saving, intelligent, and easy solutions. It ensures that a scalable, secure, high-quality power supply is available for any critical high-density computer and IT environment applications, such as data centers and other critical loads.
Product Description
The EA660 modular UPS is a scalable three-phase uninterruptible power supply system with DSP technology and provides true on-line double conversion power protection. The available UPS power and redundancy level can expand vertically from 50 to 600 kVA/600 kW in one single power cabinet, and four power cabinets can be connected in parallel, increasing the capacity up to 2.4 M kW. It features a modular hot-swappable design; all modules support plug & play, including power modules, bypass modules, and control modules, which simplifies UPS servicing and maintenance.
Features
Highlights
Features
Specification
MODEL |
EA66200 |
EA66300 |
EA66400 |
EA66500 |
EA66600 |
||
Rated capacity |
200kVA/200kW |
300kVA/300kW |
400kVA/400kW |
500kVA/500kW |
600kVA/600kW |
||
Numbers of power modules |
4 |
6 |
8 |
10 |
12 |
||
Rated capacity of power module |
50kVA |
||||||
INPUT |
|||||||
Input wiring |
3Ph+N+PE |
||||||
Rated voltage |
380/400/415Vac |
||||||
Voltage range |
138~485Vac (304~485Vac without power downgrading; 138~304Vac with linear downgrading 40%) |
||||||
Input frequency |
40~70Hz |
||||||
Power factor |
≥ 0.99 |
||||||
Current distortion |
< 3% |
||||||
BATTERIES |
|||||||
Battery voltage |
± 240Vdc (±180,±192,±204,±216,±228,±252,±264,±276 selectable) |
||||||
Number of battery |
40 pcs12 V batteries ( 30/32/34/36/38/42/44/46pcs selectable) |
||||||
OUTPUT |
|||||||
Output wiring |
3Ph+N+PE |
||||||
Rated voltage |
380/400/415Vac±1% |
||||||
Frequency |
Synchronized with utility in mains power mode: 50Hz/60Hz±0.25% in battery mode |
||||||
Power factor |
1 |
||||||
Voltage distortion |
≤ 1% with linear load/≤ 3 % with non-linear load |
||||||
Crest factor |
3:1 |
||||||
Inverter overload capacity |
105% < load ≤ 110%: transfer to bypass in 60min 110% < load ≤ 125%: transfer to bypass in 10min 125% < load ≤ 150%: transfer to bypass in 1min Load > 150%: transfer to bypass in 200ms |
||||||
Bypass overload capacity |
Load ≤135% for long term; < 1000% load for 100ms |
||||||
SYSTEM |
|||||||
Efficiency |
96.5% |
||||||
Max. number of parallel connections |
4units |
||||||
Transfer time |
0ms |
||||||
Protections |
Short circuit protection, overload protection, over-temperature protection, battery low voltage protection, output over/low voltage protection, fans failure protection etc. |
||||||
Communications |
RS485, dry contacts, SNMP |
||||||
Display |
7 inches LCD touch screen |
||||||
OTHERS |
|||||||
Operating temperature |
0~40℃ |
||||||
Storage temperature |
-40℃~+70℃ |
||||||
Humidity |
0~95%(non-condensing) |
||||||
Altitude |
≤1000m. Above 1000m, derating 1% for each additional 100m |
||||||
Protection level |
IP 20 |
||||||
Noise level at 1 m |
< 65dB |
< 68dB |
|||||
Cabinet dimensions (WxDxH) (mm) |
600×850×2000 |
1200×850×2000 |
1400×850×2000 |
||||
UPS module dimensions (WxDxH) (mm) |
440×620×130 |
||||||
Cabinet weight (kg) |
233 |
242 |
415 |
465 |
617 |
||
Power module weight (kg) |
32 |