The EA800 is a high-performance, reliable transformer-based UPS system suitable for various critical applications, such as data centers and industrial automation. It offers stable and dependable power protection, meeting the needs of users in diverse settings.
Product Description
The EA800 is a transformer-based UPS system designed to address power fluctuations and supply interruptions, providing reliable power protection. With a capacity range of 6–30 kVA, it supports both 1:1 and 3:1 input/output ratios to meet the diverse requirements of different application environments.
Features
Rear Panel
Product Specification
MODEL |
EA806 (1:1) |
EA810 (1:1) |
EA810 (3:1) |
EA815 (3:1) |
EA820 (3:1) |
EA830 (3:1) |
||||
Capacity |
6kVA/4800W |
10kVA/8kW |
10kVA/8kW |
15kVA/12kW |
20kVA/16kW |
30kVA/24kW |
||||
INPUT |
||||||||||
Input wiring |
Single-phase three-wire (1Φ+N+PE) |
Three-phase five-wire (3Φ+N+PE) |
||||||||
Rated voltage |
220/230/240Vac |
380/400/415Vac |
||||||||
Voltage range |
165~275Vac |
285~475Vac |
||||||||
Rated frequency |
50/60Hz |
|||||||||
Frequency range |
40~70Hz |
|||||||||
Bypass voltage range |
±25% (settable) |
|||||||||
OUTPUT |
||||||||||
Output wiring |
Single-phase three-wire (1Φ+N+PE) |
|||||||||
Rated voltage |
220/230/240Vac |
|||||||||
Output voltage regulation |
±1% |
|||||||||
Rated frequency |
50/60Hz(settable) |
|||||||||
Output frequency regulation |
50/60Hz±0.1Hz in battery mode |
|||||||||
Waveform |
Sinusoidal |
|||||||||
Power factor |
0.8 |
|||||||||
Voltage distortion (THDv) |
≤ 2% (linear load); ≤ 5% (non-linear load) |
|||||||||
Crest factor |
3:1 |
|||||||||
Overload |
105%~125% for 10min, 125%~150% for 1min, 150%~200% for 200ms, > 200% for 100ms |
|||||||||
BATTERIES |
||||||||||
DC voltage |
192Vdc |
|||||||||
Number of batteries |
12Vx16pcs |
|||||||||
Charging voltage |
216Vdc |
|||||||||
EOD |
168Vdc |
|||||||||
Charging current |
Default 8A (2A/4A/6A/8A/10A/12A selectable) |
|||||||||
SYSTEM |
||||||||||
Max. number of parallel connections |
/ |
2 |
||||||||
Protections |
Short-circuit, overload, overvoltage, undervoltage, low battery, overtemperature |
|||||||||
Communications |
RS232/USB (standard); RS485/SNMP/dry contacts (optional) |
|||||||||
OTHERS |
||||||||||
Operating temperature |
0~40℃ |
|||||||||
Storage temperature |
-25℃~55℃ (without batteries) |
|||||||||
Relative humidity |
0~95% (non-condensing) |
|||||||||
Altitude |
≤ 1000m (derating 1% for each additional 100 m) |
|||||||||
IP rating |
IP 20 |
|||||||||
Noise level at 1 m |
< 60dB |
|||||||||
Dimensions (W×D×H) (mm) |
210x585x590 |
310x600x880 |
400x815x1100 |
|||||||
Packaged dimensions (W×D×H) (mm) |
328x716x805 |
430x710x1080 |
525x925x1305 |
|||||||
Net weight (kg) |
54 |
104 |
140 |
210 |
240 |
280 |
||||
Gross weight (kg) |
64 |
113 |
153 |
225 |
255 |
295 |
For critical systems related to public safety or significant economic benefits, a dual-power system is required to power the load.