EA800 6-30kVA (1:1/3:1) Online Transform-based UPS
uninterruptible power supply types, uninterruptible power supply unit, uninterruptible power supply ups manufacturers, use of uninterruptible power supply, uninterruptible power supply size
  • uninterruptible power supply types, uninterruptible power supply unit, uninterruptible power supply ups manufacturers, use of uninterruptible power supply, uninterruptible power supply size

EA800 6-30kVA (1:1/3:1) Online Transform-based UPS

The EA800 is a high-performance, reliable transformer-based UPS system suitable for various critical applications, such as data centers and industrial automation. It offers stable and dependable power protection, meeting the needs of users in diverse settings.

Contact us
Inquiry Basket
OEM:
Available
Sample:
Available
Payment:
Other
Place of Origin:
China
Supply Ability:
10 piece per Week

Product Description

The EA800 is a transformer-based UPS system designed to address power fluctuations and supply interruptions, providing reliable power protection. With a capacity range of 6–30 kVA, it supports both 1:1 and 3:1 input/output ratios to meet the diverse requirements of different application environments.


Features

  • Single-phase, three-phase, and single-phase models with on-line double conversion technology
  • DSP (Digital Signal Processors) technology
  • Suitable for all kinds of loads (resistive, inductive, and non-linear loads, etc.)
  • High overload capability (up to 150%)
  • Bypass dual DSP control design to enhance more reliability (10–30k)
  • Supports dual input,hot standby in series
  • Redundant and parallelable with advanced parallel current-sharing control technology (10–30 kVA)
  • Cold start and mains start functions
  • High charging capability: 2 A/4 A/6 A/8 A/10 A/12 A selectable (standard), 14 A/16 A/18 A/20 A/22 A/24 A selectable (options) (10-30k)
  • Standard configuration with an output isolation transformer
  • Superior protection (surge, short-circuit, overvoltage, undervoltage, overcharge, reverse battery protection, etc.)
  • Advanced communications: RS232 and USB ports (standard), SNMP, dry contacts, and RS485 (options)
  • Other options (parallel kits, input isolation transformer, bypass isolation transformer, and harmonic suppressor)


Rear Panel


Product Specification

MODEL

EA806 (1:1)

EA810 (1:1)

EA810 (3:1)

EA815 (3:1)

EA820 (3:1)

EA830 (3:1)

Capacity

6kVA/4800W

10kVA/8kW

10kVA/8kW

15kVA/12kW

20kVA/16kW

30kVA/24kW

INPUT

Input wiring

Single-phase three-wire (1Φ+N+PE)

Three-phase five-wire  (3Φ+N+PE)

Rated voltage

220/230/240Vac

380/400/415Vac

Voltage range

165~275Vac

285~475Vac

Rated frequency

50/60Hz

Frequency range

40~70Hz

Bypass voltage range

±25% (settable)

OUTPUT

Output wiring

Single-phase three-wire (1Φ+N+PE)

Rated voltage

220/230/240Vac

Output voltage regulation

±1%

Rated frequency

50/60Hz(settable)

Output frequency regulation

50/60Hz±0.1Hz in battery mode

Waveform

Sinusoidal

Power factor

0.8

Voltage distortion

(THDv)

≤ 2% (linear load); ≤ 5% (non-linear load)

Crest factor

3:1

Overload

105%~125% for 10min, 125%~150% for 1min, 150%~200% for 200ms, > 200% for 100ms

BATTERIES

DC voltage

192Vdc

Number of batteries

12Vx16pcs

Charging voltage

216Vdc

EOD

168Vdc

Charging current

Default 8A (2A/4A/6A/8A/10A/12A selectable)

SYSTEM

Max. number of parallel connections

/

2

Protections

Short-circuit, overload, overvoltage, undervoltage, low battery, overtemperature

Communications

RS232/USB (standard); RS485/SNMP/dry contacts (optional)

OTHERS

Operating temperature

0~40℃

Storage temperature

-25℃~55℃ (without batteries)

Relative humidity

0~95% (non-condensing)

Altitude

≤ 1000m (derating 1% for each additional 100 m)

IP rating

IP 20

Noise level at 1 m

< 60dB

Dimensions

(W×D×H) (mm)

210x585x590

310x600x880

400x815x1100

Packaged dimensions

(W×D×H) (mm)

328x716x805

430x710x1080

525x925x1305

Net weight (kg)

54

104

140

210

240

280

Gross weight (kg)

64

113

153

225

255

295

  • This product is applicable to industrial, commercial, financial, rail transit, and other industry applications but is not available for life support systems.
  • For critical systems related to public safety or significant economic benefits, a dual-power system is required to power the load.

Contact us